CSB UPS122406 VRLA Battery 12V 240W
The UPS122406 is a 12V pure lead VRLA battery from CSB. Its 240W rating is the 5-minute rate power. It is primarily used with data center UPS systems and can be used in float standby service, with a design life of up to 5 years.
Taobao store
WeChat procurement
Product Features
- Valve-regulated lead-acid (VRLA) design
- Maintenance-free with absorbent glass mat (AGM) technology, achieving up to 99% gas recombination efficiency
- Pure lead plates with proprietary formulation elements
- Engineered for high-rate UPS and float standby power applications
- Manufactured in compliance with IEC 61056-1/2:2012 and UL1989 certified (MH14533)
Application Scenarios
- UPS backup battery, suitable for data centers
- Uninterruptible power supply for server rooms, server backup solution
- High-power backup, dedicated for industrial UPS
- Emergency power, paired with medical equipment UPS
- Backup solution, selected for financial system UPS
- Standby power, configured for communication room UPS
Product parameters
- Model:UPS122406
- Voltage:12 Vdc
- Nominal Capacity:240W @5min-rate
- Watts per Cell:38.83 (5-Min 1.67 VPC @ 25°)
- Watts per Cell:18.5 (15-Min 1.67 VPC @ 25°)
- Max. Charge Current:2.00 A
- Max. Discharge Current:130 A
- Short Circuit Current:230 A
- Internal Resistance:33.50 mΩ
- Terminal Type:F2 terminal (Faston Tab 250)
- Container Material:ABS (UL 94-HB) standard, flame-retardant (94-V0) available upon request
- Weight:1.46 / 3.22 kg / lb.
- Length (L):150.9±2.0 / 5.94±0.08 mm / in
- Width (W):51.0±1.0 / 2.01±0.04 mm / in
- Height (H):98.6±1.0 / 3.88±0.04 mm / in
- Design Life:Up to 5 years in standby service at 25°C; Eurobat (20°C): 3-5 years, Standard Commercial
- Float Charging Voltage:13.5 - 13.8 Vdc/battery
- Equalizing Charging Voltage:14.4 - 15.0 Vdc/battery
- Operating Temperature:discharge -15°C to 50°C; charge/storage -15°C to 40°C
- Note:F1 terminal is available; Max Discharge Current = 100 A (5 sec.)
Product details
The CSB UPS122406 is part of the UPS series, which includes 6V and 12V top-terminal VRLA batteries. It uses absorbed glass mat (AGM) technology, achieves up to 99% gas recombination efficiency, and requires zero maintenance. The pure lead construction makes this series particularly suitable for high-rate discharge and float standby applications in uninterruptible power supplies (UPS). The official listed application is data center UPS.
In terms of electrical specifications, the UPS122406 has a nominal voltage of 12 Vdc and a nominal capacity calculated at 9.60V per PCS @ 25°C, 240W @5min-rate. The per-cell power is 38.83 W/cell at 5 minutes 1.67 VPC @ 25°C and 18.5 W/cell at 15 minutes 1.67 VPC @ 25°C. The maximum charge current is 2.00 A, the maximum discharge current is 130 A, the short-circuit current is 230 A, and the internal resistance is 33.50 mΩ. The float charge voltage is 13.5 to 13.8 Vdc/battery at 25°C, and the equalize charge voltage is 14.4 to 15.0 Vdc/battery at 25°C.
The terminal is F2 terminal - Faston Tab 250. The case material is ABS (UL 94-HB), and a flame-retardant (94-V0) version is available upon request. Dimensions are 150.9±2.0 mm long, 51.0±1.0 mm wide, and 98.6±1.0 mm high, with a weight of approximately 1.46 kg. The design life is up to 5 years in float standby service at 25°C, and 3 to 5 years per the Eurobat (20°C) standard for commercial use. Operating temperature: nominal 25°C (77°F), discharge range -15°C to 50°C (5°F to 122°F), charge and storage range -15°C to 40°C (5°F to 104°F).
In terms of self-discharge, self-discharge is less than 10% after 90 days of storage at 25°C (77°F), and storage is possible for up to 6 months. The battery must be fully charged before use, and if the storage temperature is above 25°C (77°F), it must be charged earlier. The product complies with IEC 61056-1/2:2012 and is recognized to UL1989 (MH14533). With these features, the battery is suitable for data center UPS and other scenarios requiring high-rate discharge and float standby.