Product Features

  • Valve-regulated lead-acid (VRLA) design
  • Maintenance-free, with gas recombination efficiency up to 99% thanks to absorbent glass mat (AGM) technology
  • Pure lead construction with proprietary elements
  • Suitable for high-rate UPS and float standby power applications
  • Manufactured to IEC 61056-1/2:2012 and UL1989 certified (MH14533)

Application Scenarios

  • UPS backup power for data centers
  • Uninterruptible power systems for server rooms
  • High-power backup solutions for industrial UPS
  • Emergency UPS power for medical equipment
  • UPS backup power for financial systems
  • UPS backup power for telecom equipment rooms

Product parameters

  • Model:UPS12460
  • Voltage:12 Vdc
  • Nominal Capacity:460W @5min-rate
  • Watts per Cell:74.00 (5-Min 1.67 VPC @ 25°)
  • Watts per Cell:36.83 (15-Min 1.67 VPC @ 25°)
  • Max. Charge Current:3.80 A
  • Max. Discharge Current:130 A
  • Short Circuit Current:450 A
  • Internal Resistance:16.60 mΩ
  • Terminal Type:F2 terminal (Faston Tab 250)
  • Container Material:ABS (UL 94-HB) standard, flame-retardant (94-V0) available upon request
  • Weight:2.50 / 5.51 kg / lb.
  • Length (L):150.9±2.0 / 5.94±0.08 mm / in
  • Width (W):64.8±1.0 / 2.55±0.04 mm / in
  • Height (H):98.6±1.0 / 3.88±0.04 mm / in
  • Design Life:Up to 5 years in standby service at 25°C; Eurobat (20°C): 3-5 years, Standard Commercial
  • Float Charging Voltage:13.5 - 13.8 Vdc/battery
  • Equalizing Charging Voltage:14.4 - 15.0 Vdc/battery
  • Operating Temperature:discharge -15°C to 50°C; charge/storage -15°C to 40°C

Product details

The CSB UPS12460 belongs to the UPS product line, which covers 6V and 12V top-terminal VRLA-AGM batteries officially designated for data center uninterruptible power supplies. This series is positioned as high-power pure lead batteries developed for UPS applications. For this specific model, the nominal voltage is 12 Vdc, and the nominal capacity is 460W at the 5-minute rate at 9.60V per PCS @ 25°C. In terms of cell power, it delivers 74.00 W/cell at 5 minutes at 1.67 VPC @ 25°C and 36.83 W/cell at 15 minutes at 1.67 VPC @ 25°C. Electrically, the UPS12460 withstands a maximum charge current of 3.80 A and a maximum discharge current of 130 A, with a short-circuit current of 450 A and an internal resistance of 16.60 mΩ. At 25°C, the float charge voltage range is 13.5 to 13.8 Vdc/battery, and the equalization charge voltage range is 14.4 to 15.0 Vdc/battery. Self-discharge characteristics are as follows: stored at 25°C for 90 days, capacity loss is less than 10%, with a maximum storage of 6 months. A full charge is required before putting the battery into service, and if storage temperature exceeds 25°C, a supplementary charge should be applied in advance. Structurally, the battery uses a valve-regulated sealed lead-acid design with absorbed glass mat (AGM) technology, achieving gas recombination efficiency of up to 99%, along with a pure lead construction and proprietary elements. The case material is ABS (UL 94-HB), with a flame-retardant grade (94-V0) available upon request. Terminals are F2 terminal - Faston Tab 250. Dimensions are 150.9±2.0 mm in length, 64.8±1.0 mm in width, and 98.6±1.0 mm in height, with a weight of 2.50 kg. In terms of temperature adaptability and service life, the nominal operating temperature is 25°C, discharge is permitted from -15°C to 50°C, and charging and storage are between -15°C and 40°C. Design life reaches 5 years under 25°C float standby conditions; according to the Eurobat (20°C) standard, commercial applications are 3 to 5 years. The product is manufactured to IEC 61056-1/2:2012 and is UL1989 recognized (MH14533). Given the above characteristics, the UPS12460 is suitable for data center UPS float standby applications, with a design focus on high-rate discharge and maintenance-free operation, meeting the requirements of float standby power scenarios for battery consistency, sealing, and gas recombination efficiency.