HR12120W 12V Valve-Regulated Sealed Lead-Acid Battery CSB
CSB HR12120W is a 12V valve-regulated sealed lead-acid battery utilizing AGM technology and pure lead construction, primarily intended for float standby applications such as data center UPS. The 15-minute rate nominal capacity reaches 120W, while the 5-minute rate is 232.17 W/cell, with a design float life of up to 5 years.
Taobao store
WeChat procurement
Product Features
- Valve-regulated lead-acid (VRLA) design
- Absorbent glass mat (AGM) technology, maintenance-free, with up to 99% gas recombination efficiency
- Pure lead plates with proprietary formulation elements
- Engineered for high-rate UPS and float standby power applications
- Manufactured to IEC 61056-1/2:2012 and UL1989 certified (MH14533)
Application Scenarios
- UPS backup for small and medium data centers
- UPS for server racks
- Emergency power for network equipment rooms
- UPS backup power for medical imaging equipment
- Fast discharge UPS in industrial control applications
- Backup power for precision laboratory instruments
Product parameters
- Model:HR12120W
- Voltage:12 Vdc
- Nominal Capacity:120W @15min-rate
- Watts per Cell:232.17 (5-Min 1.67 VPC @ 25°)
- Watts per Cell:123 (15-Min 1.67 VPC @ 25°)
- Max. Charge Current:12 A
- Max. Discharge Current:225 A
- Short Circuit Current:928 A
- Internal Resistance:8.2 mΩ
- Terminal Type:I1 thread lead alloy recessed terminal to accept M5 bolt
- Terminal Torque:30.4±6.1 Kgf·cm / 26.4±5.3 Lbf·in / 3.0±0.6 N·m
- Container Material:ABS (UL 94-HB) standard, flame-retardant (94-V0) available upon request
- Weight:10.2 / 20.48 kg / lb.
- Length (L):166±2.0 / 6.54±0.08 mm / in
- Width (W):125±1.5 / 4.92±0.06 mm / in
- Height (H):175±2.0 / 6.89±0.08 mm / in
- Design Life:Up to 5 years in standby service at 25°C; Eurobat (20°C): 3-5 years, Standard Commercial
- Float Charging Voltage:13.5 - 13.8 Vdc/battery
- Equalizing Charging Voltage:14.4 - 15.0 Vdc/battery
- Operating Temperature:discharge -15°C to 50°C; charge/storage -15°C to 40°C
Product details
Within the CSB product line, the HR12120W belongs to the HR series of high-rate discharge pure lead batteries. It is a 12V top-terminal valve-regulated sealed lead-acid battery, with the official designated application being data center uninterruptible power supplies. This series is specifically designed for lower-output UPS systems and backup scenarios requiring rapid discharge, positioned as a high-rate discharge pure lead battery. This battery combines valve-regulated sealed lead-acid construction with absorbed glass mat technology, achieving gas recombination efficiency of up to 99%, offering maintenance-free characteristics, and, by virtue of its pure lead construction and proprietary element formulation, is suitable for high-rate UPS and float standby power applications.
In terms of electrical specifications, the HR12120W has a voltage of 12 Vdc and a nominal capacity of 120W @15min-rate (1.67 VPC @25°C). Its 5-minute rate power is 232.17 W/cell, and its 15-minute rate power is 123 W/cell (both at 1.67 VPC @25°C). The maximum charging current is 12 A, the maximum discharge current is 225 A, the short-circuit current reaches 928 A, and the internal resistance is 8.2 mΩ. The float charging voltage range is 13.5 to 13.8 Vdc/battery (25°C), while the equalization charging voltage is 14.4 to 15.0 Vdc/battery (25°C).
Regarding mechanical construction, the battery terminal uses an I1-Thread lead alloy recessed terminal to accept M5 bolt, with terminal torque of 30.4±6.1 Kgf·cm, 26.4±5.3 Lbf·in, or 3.0±0.6 N·m. The case material is ABS (UL 94-HB), and a flame-retardant (94-V0) version can also be provided upon request. The weight is 10.2 kg (20.48 lb), and the dimensions are length 166±2.0 mm, width 125±1.5 mm, and height 175±2.0 mm.
Regarding operating temperature, the nominal temperature is 25°C, the allowable discharge range is -15°C to 50°C, and the charging and storage temperature range is -15°C to 40°C. Under 25°C float standby conditions, the design life can reach 5 years; according to the Eurobat (20°C) standard, the commercial life is 3 to 5 years. For self-discharge, it is less than 10% after 90 days, and it can be stored for up to 6 months at 25°C; it must be fully charged before use. If the storage temperature exceeds 25°C, charging is required earlier. This product is manufactured in accordance with IEC 61056-1/2:2012 and has obtained UL1989 Recognized (MH14533).