CSB HR1227W 12V 27W Valve-Regulated Sealed Lead-Acid Battery
The CSB HR1227W battery is a 12V valve-regulated sealed lead-acid type that uses AGM technology and a pure lead construction, with a 15-minute rate nominal capacity of 27W, primarily serving data center UPS and other float standby power applications.
Taobao store
WeChat procurement
Product Features
- Valve-regulated lead-acid (VRLA) design
- Absorbent glass mat (AGM) technology, maintenance-free, with gas recombination efficiency up to 99%
- Pure lead construction with proprietary elements
- Suitable for high-rate UPS and float standby power applications
- Manufactured to IEC 61056-1/2:2012 and UL1989 certified (MH14533)
Application Scenarios
- Backup UPS for small and medium data centers
- Uninterruptible power supply for server racks
- Emergency power for network equipment rooms
- Uninterruptible power backup for medical imaging equipment
- High-rate discharge for industrial control UPS
- Backup power for precision laboratory instruments
Product parameters
- Model:HR1227W
- Voltage:12 Vdc
- Nominal Capacity:27W @15min-rate
- Watts per Cell:53.0 (5-Min 1.67 VPC @ 25°)
- Watts per Cell:27.0 (15-Min 1.67 VPC @ 25°)
- Max. Charge Current:2.70 A
- Max. Discharge Current:130 A
- Short Circuit Current:424 A
- Internal Resistance:19.9 mΩ
- Terminal Type:F2 terminal (Faston Tab 250)
- Container Material:ABS (UL 94-HB) standard, flame-retardant (94-V0) available upon request
- Weight:1.97 / 4.34 kg / lb.
- Length (L):90.0±1.0 / 3.54±0.04 mm / in
- Width (W):70.0±1.0 / 2.76±0.04 mm / in
- Height (H):106.1±1.5 / 4.18±0.06 mm / in
- Design Life:Up to 5 years in standby service at 25°C; Eurobat (20°C): 3-5 years, Standard Commercial
- Float Charging Voltage:13.5 - 13.8 Vdc/battery
- Equalizing Charging Voltage:14.4 - 15.0 Vdc/battery
- Operating Temperature:discharge -15°C to 50°C; charge/storage -15°C to 40°C
- Note:F1 terminal is available; Max Discharge Current = 100 A
Product details
In CSB's product line, the HR1227W belongs to the HR series and is a 12V valve-regulated sealed lead-acid battery with top terminal design. It uses absorbent glass mat (AGM) technology, with gas recombination efficiency of up to 99%; combined with pure lead construction and a proprietary formula, this battery is built for high-rate discharge and float standby power scenarios. As a model in this high-rate discharge pure lead battery series, it is officially aimed at UPS with lower output power and fast-discharge standby needs, with data center uninterruptible power supplies as its official application direction.
In terms of electrical specifications, the HR1227W voltage is 12 Vdc; at 1.67 VPC, 25°C, its nominal capacity is 27W at the 15-minute rate. Also at 1.67 VPC, 25°C, the 5-minute rate power is 53.0 W/cell, and the 15-minute rate power is 27.0 W/cell. The maximum charge current is 2.70 A, the maximum discharge current is 130, the short-circuit current is 424 A, and the internal resistance is 19.9 mΩ. The float charge voltage requires 13.5 to 13.8 Vdc/battery (25°C), and the equalization charge voltage is 14.4 to 15.0 Vdc/battery (25°C).
In terms of construction and dimensions, the battery is equipped with F2-Faston Tab250 terminals, and the case uses ABS material (UL 94-HB); a flame-retardant 94-V0 version can also be provided if required. Its weight is 1.97 kg (4.34 lb), with a length of 90.0±1.0 mm, a width of 70.0±1.0 mm, and a height of 106.1±1.5 mm. For design life, it can last up to 5 years under 25°C float charge conditions; according to the Eurobat (20°C) standard, the commercial life is 3 to 5 years.
For operating temperature, the nominal temperature is 25°C (77°F); the allowable discharge range is -15°C to 50°C (5°F to 122°F), and charging and storage are between -15°C and 40°C (5°F to 104°F). For self-discharge rate, it is less than 10% after 90 days of storage at 25°C; the battery can be stored at 25°C for up to 6 months, but must be fully charged before use. If the storage temperature exceeds 25°C, charging is required earlier.
This battery is maintenance-free, manufactured according to IEC 61056-1/2:2012, and recognized under UL1989 (MH14533). With high-rate discharge capability and stable float charge performance, the HR1227W is well suited for data center UPS and other applications requiring fast discharge and standby power; under the specified float charge voltage and temperature conditions, it can maintain reliable operation.