CSB HR1232W 12V 32W Valve-Regulated Sealed Lead-Acid Battery
The CSB HR1232W is a 12V valve-regulated sealed lead-acid battery in the HR series. Utilizing pure lead and AGM technology, it delivers a nominal capacity of 32W at the 15-minute rate and is primarily designed for float standby power applications such as data center UPS systems.
Taobao store
WeChat procurement
Product Features
- Valve-regulated lead-acid (VRLA) design
- Maintenance-free, with gas recombination efficiency up to 99% through absorbent glass mat (AGM) technology
- Utilizes pure lead construction and proprietary formulation elements
- Engineered for high-rate UPS and float standby power requirements
- Manufactured to IEC 61056-1/2:2012 standards and UL1989 certified (MH14533)
Application Scenarios
- Uninterruptible power supply for server racks
- UPS backup for small and medium data centers
- UPS backup for medical imaging equipment
- Emergency power protection for network equipment rooms
- Backup power for precision laboratory instruments
- Fast discharge for industrial control UPS
Product parameters
- Model:HR1232W
- Voltage:12 Vdc
- Nominal Capacity:32W @15min-rate
- Watts per Cell:66.1 (5-Min 1.67 VPC @ 25°)
- Watts per Cell:32.0 (15-Min 1.67 VPC @ 25°)
- Max. Charge Current:3.20 A
- Max. Discharge Current:130 A
- Short Circuit Current:335 A
- Internal Resistance:22.7 mΩ
- Terminal Type:F2 terminal (Faston Tab 250)
- Container Material:ABS (UL 94-HB) standard, flame-retardant (94-V0) available upon request
- Weight:2.34 / 5.16 kg / lb.
- Length (L):150.9±2.0 / 5.94±0.08 mm / in
- Width (W):64.8±1.0 / 2.55±0.04 mm / in
- Height (H):98.6±1.0 / 3.88±0.04 mm / in
- Design Life:Up to 5 years in standby service at 25°C; Eurobat (20°C): 3-5 years, Standard Commercial
- Float Charging Voltage:13.5 - 13.8 Vdc/battery
- Equalizing Charging Voltage:14.4 - 15.0 Vdc/battery
- Operating Temperature:discharge -15°C to 50°C; charge/storage -15°C to 40°C
Product details
The CSB HR1232W is a 12V top-terminal valve-regulated sealed lead-acid battery in the HR series. It features a pure lead construction with a proprietary element formulation, combined with Absorbent Glass Mat (AGM) technology, achieving gas recombination efficiency of up to 99% in a maintenance-free design. The HR series is engineered for high-rate discharge, making it suitable for UPS and standby applications with lower power output that require rapid discharge. Its officially designated application is data center uninterruptible power supplies.
Specifications: The HR1232W has a voltage of 12 Vdc; at 1.67 VPC, 25°C, the nominal capacity is 32W @15min-rate. In terms of power performance, at the 5-minute rate, 1.67 VPC, 25°C, it delivers 66.1 W per cell; at the 15-minute rate, 1.67 VPC, 25°C, it delivers 32.0 W per cell. Maximum charge current is 3.20 A, maximum discharge current is 130 A, short-circuit current is 335 A, and internal resistance is 22.7 mΩ.
Charging and temperature conditions: At 25°C, the float charge voltage range is 13.5 to 13.8 Vdc/battery, and the equalize charge voltage range is 14.4 to 15.0 Vdc/battery. The nominal operating temperature is 25°C; discharge can be performed from -15°C to 50°C, while charging and storage are between -15°C and 40°C. The self-discharge rate is less than 10% after 90 days of storage at 25°C. The battery can be stored for up to 6 months and must be fully charged before use; if storage temperature exceeds 25°C, recharge should be performed earlier.
Dimensions: The HR1232W measures 150.9±2.0 mm in length, 64.8±1.0 mm in width, and 98.6±1.0 mm in height, weighing 2.34 kg. The terminal type is F2-Faston Tab250. The case is made of ABS material, compliant with UL 94-HB, and a flame-retardant 94-V0 version is also available upon request. Design life is up to 5 years under float charge at 25°C, and 3 to 5 years per the Eurobat 20°C standard for commercial use.
This product is manufactured in accordance with IEC 61056-1/2:2012 and is recognized under UL1989, recognition number MH14533. Thanks to its high-rate discharge characteristics and float standby design, the HR1232W is suitable for applications such as data center UPS systems that require rapid discharge backup, and can be used in continuous float charge at 25°C according to the float charge voltage specified above.