Product Features

  • Valve-regulated lead-acid (VRLA) design
  • AGM absorbed glass mat technology, maintenance-free with up to 99% gas recombination efficiency
  • Proprietary formulation with pure lead construction
  • Suitable for float standby and high-rate UPS applications
  • UL1989 certified (MH14533) and manufactured to IEC 61056-1/2:2012 standards

Application Scenarios

  • High-voltage DC backup power for cloud computing centers
  • UPS backup power for large data centers
  • UPS emergency support for core communication nodes
  • Uninterruptible power for financial trading platforms
  • UPS backup for rail transit signaling systems
  • High-power UPS backup for industrial automation

Product parameters

  • Model:HRL12150W
  • Voltage:12 Vdc
  • Nominal Capacity:150W @15min-rate
  • Watts per Cell:271 (5-Min 1.67 VPC @ 25°)
  • Watts per Cell:156 (15-Min 1.67 VPC @ 25°)
  • Max. Charge Current:15.0 A
  • Max. Discharge Current:225 A
  • Short Circuit Current:1116 A
  • Internal Resistance:7.30 mΩ
  • Terminal Type:I2 thread lead alloy terminal to accept M6 bolt
  • Terminal Torque:51.7±10.3 Kgf·cm / 44.9±9.0 Lbf·in / 5.10±1.0 N·m
  • Container Material:ABS (UL 94-HB) standard, flame-retardant (94-V0) available upon request
  • Weight:11.95 / 26.34 kg / lb.
  • Length (L):195.6±2.0 / 7.70±0.08 mm / in
  • Width (W):130.0±1.5 / 5.12±0.06 mm / in
  • Height (H):174.8±2.0 / 6.88±0.08 mm / in
  • Design Life:Up to 10 years in standby service at 25°C; Eurobat (20°C): 10-12 years, Standard Commercial
  • Float Charging Voltage:13.5 - 13.8 Vdc/battery
  • Equalizing Charging Voltage:14.4 - 15.0 Vdc/battery
  • Operating Temperature:discharge -15°C to 50°C; charge/storage -15°C to 40°C

Product details

The CSB HRL series includes 6V and 12V top-terminal VRLA batteries, and the HRL12150W is one of them, with a nominal voltage of 12 Vdc. At 25°C and 1.67 VPC, the 15-minute rate nominal capacity is 150W; in terms of power per cell, it reaches 271 W/cell at 5 minutes, 1.67 VPC, 25°C, and 156 W/cell at 15 minutes, 1.67 VPC, 25°C. This series is officially positioned as long-life, high-rate UPS pure lead batteries, mainly serving high-power data centers and UPS loads, with the officially listed application being data center UPS. In terms of electrical specifications, the HRL12150W can withstand a maximum charge current of 15.0 A, a maximum discharge current of 225 A, a short-circuit current of 1116 A, and an internal resistance of 7.30 mΩ. Float voltage is set at 13.5 to 13.8 Vdc/battery (25°C), and equalize voltage is 14.4 to 15.0 Vdc/battery (25°C). For self-discharge, after 90 days at 25°C, capacity loss is less than 10%; the battery can be stored at 25°C for up to 6 months, but must be fully charged before use. If storage temperature exceeds 25°C, recharge is required earlier. In terms of structural design, the battery uses VRLA technology and an absorbed glass mat separator, with gas recombination efficiency of up to 99%, and is maintenance-free. The positive and negative plates are constructed of pure lead with a proprietary element formulation, suitable for high-rate UPS and float standby power applications. Manufacturing is based on IEC 61056-1/2:2012, and it is UL1989 recognized (MH14533). The case material is ABS (UL 94-HB); a flame-retardant 94-V0 version is available upon request. In terms of dimensions and installation, the HRL12150W is 195.6±2.0 mm long, 130.0±1.5 mm wide, and 174.8±2.0 mm high, weighing 11.95 kg. The terminals use I2 threaded lead alloy and can be used with M6 bolts; terminal torque is 51.7±10.3 Kgf·cm, 44.9±9.0 Lbf·in, or 5.10±1.0 N·m. For temperature conditions, the nominal temperature is 25°C, discharge is allowed from -15°C to 50°C, and charge and storage are allowed from -15°C to 40°C. For design life, it can reach 10 years in 25°C float standby service; under Eurobat (20°C) standard commercial conditions, it is 10 to 12 years.
link
Go to purchase
Telephone
13775032303
email
powercube@foxmail.com
wechat
wechat
Loading...