CSB HRL1234W 12V 34W VRLA Battery
The CSB HRL1234W is a 12V VRLA battery in the HRL series with a 15-minute rate nominal capacity of 34W. Combining pure lead and AGM technology, it is suitable for data center UPS and other high-rate float standby power applications.
Taobao store
WeChat procurement
Product Features
- VRLA (valve-regulated lead-acid) design
- AGM absorbed glass mat technology with up to 99% gas recombination efficiency, completely maintenance-free
- Equipped with pure lead plates and proprietary formulation elements
- Engineered for high-rate UPS and float standby power applications
- Manufactured in compliance with IEC 61056-1/2:2012 and UL1989 certified (File No. MH14533)
Application Scenarios
- UPS backup solutions for large data centers
- High-voltage DC backup supporting cloud computing centers
- Uninterruptible power for financial trading systems
- UPS emergency protection for communication hub operations
- High-power UPS backup meeting industrial automation needs
- UPS backup applications for rail transit signaling
Product parameters
- Model:HRL1234W
- Voltage:12 Vdc
- Nominal Capacity:34W @15min-rate
- Watts per Cell:75.34 (5-Min 1.67 VPC @ 25°)
- Watts per Cell:35.50 (15-Min 1.67 VPC @ 25°)
- Max. Charge Current:3.40 A
- Max. Discharge Current:130 A
- Short Circuit Current:367 A
- Internal Resistance:17.0 mΩ
- Terminal Type:F2 terminal (Faston Tab 250)
- Container Material:ABS (UL 94-HB) standard, flame-retardant (94-V0) available upon request
- Weight:2.70 / 5.95 kg / lb.
- Length (L):150.9±2.0 / 5.94±0.08 mm / in
- Width (W):64.8±1.0 / 2.55±0.04 mm / in
- Height (H):98.6±1.0 / 3.88±0.04 mm / in
- Design Life:Up to 8 years in standby service at 25°C; Eurobat (20°C): 10-12 years, Standard Commercial
- Float Charging Voltage:13.5 - 13.8 Vdc/battery
- Equalizing Charging Voltage:14.4 - 15.0 Vdc/battery
- Operating Temperature:discharge -15°C to 50°C; charge/storage -15°C to 40°C
Product details
The CSB HRL1234W is part of the HRL series and is a VRLA battery available with 6V and 12V top terminal configurations, with a nominal voltage of 12 Vdc. This series is positioned as long-life, high-rate pure lead batteries, primarily addressing data center and UPS applications with higher load demands; its official designated use is data center UPS.
For capacity and power, at 25°C and 1.67 VPC, the HRL1234W has a nominal capacity of 34W @15min-rate. Also at 25°C and 1.67 VPC, per-cell power is 75.34 W/cell at the 5-minute rate and 35.50 W/cell at the 15-minute rate. The battery's maximum charge current is 3.40 A, maximum discharge current is 130 A, short-circuit current is 367 A, and internal resistance is 17.0 mΩ.
In terms of construction, the battery uses VRLA design and absorbed glass mat technology, achieving up to 99% gas recombination for maintenance-free operation; it also features pure lead construction and a proprietary element formulation. The case material is ABS (UL 94-HB), with a flame-retardant 94-V0 version available on request. The terminal type is F2 terminal - Faston Tab 250. The product is manufactured to IEC 61056-1/2:2012 and is UL1989 Recognized (MH14533).
Dimensions and weight: the battery is 150.9±2.0 mm long, 64.8±1.0 mm wide, and 98.6±1.0 mm high, weighing 2.70 kg. Design life is up to 8 years in 25°C float standby service, and 10 to 12 years under the Eurobat (20°C) standard for commercial use. The nominal operating temperature is 25°C, with a discharge range from -15°C to 50°C and a charge and storage range from -15°C to 40°C.
For charging parameters, at 25°C the float voltage is 13.5 to 13.8 Vdc/battery and the equalize voltage is 14.4 to 15.0 Vdc/battery. Self-discharge is less than 10% after 90 days at 25°C, and the battery can be stored for up to 6 months; it must be fully charged before use, and if storage temperature exceeds 25°C, recharge is required sooner. This battery is suitable for high-rate UPS and float standby power applications.