CSB HRL12390W 12V 390W VRLA Battery
As a 12V VRLA battery in the HRL series, the CSB HRL12390W delivers 390W nominal capacity at the 15-minute rate and 700W/cell at the 5-minute rate. Featuring pure lead and AGM technology, it is designed for high-rate float standby applications such as data center UPS systems.
Taobao store
WeChat procurement
Product Features
- Valve-regulated lead-acid (VRLA) design
- AGM absorbed glass mat technology, maintenance-free, with gas recombination efficiency up to 99%
- Pure lead construction with proprietary formulation elements
- Engineered for high-rate UPS and float standby power applications
- Manufactured to IEC 60896-21/22:2004 and UL1989 certified (MH14533)
Application Scenarios
- As backup power for large data center UPS
- For backup power supply of high-voltage DC systems in cloud computing centers
- Provides uninterruptible power support for financial trading systems
- Handles UPS emergency power supply tasks in communication hubs
- Meets high-power backup power requirements for industrial automation UPS
- Provides UPS backup power for rail transit signaling systems
Product parameters
- Model:HRL12390W
- Voltage:12 Vdc
- Nominal Capacity:390W @15min-rate
- Watts per Cell:700 (5-Min 1.67 VPC @ 25°)
- Watts per Cell:414 (15-Min 1.67 VPC @ 25°)
- Max. Charge Current:39.0 A
- Max. Discharge Current:800 A
- Short Circuit Current:2779 A
- Internal Resistance:3.00 mΩ
- Terminal Type:I2 thread lead alloy terminal to accept M6 bolt
- Terminal Torque:51.7±10.3 Kgf·cm / 44.9±9.0 Lbf·in / 5.10±1.0 N·m
- Container Material:PP (UL 94-HB) standard, flame-retardant (94-V0) available upon request
- Weight:33.00 / 72.73 kg / lb.
- Length (L):343.0±2.5 / 13.50±0.10 mm / in
- Width (W):170.0±2.0 / 6.69±0.08 mm / in
- Height (H):216.9±2.5 / 8.54±0.10 mm / in
- Design Life:Up to 10 years in standby service at 25°C; Eurobat (20°C): >12 years, Very Long Life
- Float Charging Voltage:13.5 - 13.8 Vdc/battery
- Equalizing Charging Voltage:14.4 - 15.0 Vdc/battery
- Operating Temperature:discharge -15°C to 50°C; charge/storage -15°C to 40°C
Product details
The HRL series covers 6V and 12V top-terminal VRLA batteries, and the CSB HRL12390W is one of them. Officially positioned as a long-life, high-rate pure lead battery, this model is primarily intended for high-power data center and UPS loads. Its rated voltage is 12 Vdc; at 25°C and 1.67 VPC, the 15-minute rate nominal capacity reaches 390W, the 5-minute rate power is 700 W/cell, and the 15-minute rate power is 414 W/cell, making it well suited for float standby scenarios requiring short-duration high-power output.
In terms of construction, the battery combines VRLA design with absorbed glass mat technology, achieving gas recombination efficiency of up to 99%, and is maintenance-free. Both positive and negative plates use pure lead construction and a proprietary formula; the official application area listed is data center uninterruptible power supplies. The case material is PP (UL 94-HB), and a flame-retardant (94-V0) version is also available upon request.
For electrical specifications, the HRL12390W has a maximum charge current of 39.0 A, maximum discharge current of 800 A, short-circuit current of 2779 A, and internal resistance of 3.00 mΩ. At 25°C, the float charge voltage ranges from 13.5 to 13.8 Vdc/battery, and the equalize charge voltage is 14.4 to 15.0 Vdc/battery. The terminals use the I2 threaded lead alloy type, compatible with M6 bolts, with a torque value of 51.7±10.3 Kgf·cm, 44.9±9.0 Lbf·in, or 5.10±1.0 N·m.
In terms of dimensions and weight, the battery is 343.0±2.5 mm long, 170.0±2.0 mm wide, and 216.9±2.5 mm high, weighing 33.00 kg (72.73 lb). The nominal operating temperature is 25°C; discharge is permitted from -15°C to 50°C, while charging and storage are permitted from -15°C to 40°C. Design life can reach 10 years under float charge at 25°C; according to the Eurobat long life standard, it can exceed 12 years at 20°C.
In terms of self-discharge performance, after 90 days of storage at 25°C, the remaining capacity is still above 90%, and storage can last up to 6 months, with a full charge required before use; if the storage temperature exceeds 25°C, earlier charging is required. This product is manufactured in accordance with IEC 60896-21/22:2004 and is UL1989 recognized (MH14533).