CSB GPL12120 12V 12Ah Valve-Regulated Sealed Lead-Acid Battery
CSB GPL12120 is a 12V 12Ah valve-regulated sealed lead-acid battery utilizing AGM technology, achieving up to 99% gas recombination efficiency, with a float design life of up to 8 years, suitable for general-purpose backup power.
Taobao store
WeChat procurement
Product Features
- VRLA (Valve Regulated Lead Acid) battery
- AGM (Absorbent Glass Mat) technology, maintenance-free, with gas recombination efficiency up to 99%
- Pure lead construction with proprietary formulation elements
- Designed for float-charge standby power applications
- Manufactured to IEC 61056-1/2:2012 and UL1989 certified (MH14533)
Application Scenarios
- Backup power for security alarm panels
- Emergency lighting and exit sign fixtures
- Backup power for medical monitors and infusion pumps
- Access control systems and building intercom equipment
- Fire alarm and linkage control panels
- Small electronic instruments and testing devices
Product parameters
- Model:GPL12120
- Voltage:12 Vdc
- Nominal Capacity:12 Ah @20hr-rate
- Ah Capacity:9.76 (8-Hr 1.75 VPC @ 25°C)
- Ah Capacity:12.00 (20-Hr 1.75 VPC @ 25°C)
- Ah Capacity:9.60 (8-Hr 1.80 VPC @ 25°C)
- Max. Charge Current:3.60 A
- Max. Discharge Current:180 A
- Short Circuit Current:458 A
- Internal Resistance:13.2 mΩ
- Terminal Type:F2 terminal (Faston Tab 250)
- Container Material:ABS (UL 94-HB) standard, flame-retardant (94-V0) available upon request
- Weight:4.10 / 9.04 kg / lb.
- Length (L):151.0±2.0 / 5.94±0.08 mm / in
- Width (W):98.0±1.0 / 3.86±0.04 mm / in
- Height (H):100.3±1.5 / 3.95±0.06 mm / in
- Design Life:Up to 8 years in standby service at 25°C; Eurobat (20°C): 10/12 years, Long Life
- Float Charging Voltage:13.5 - 13.8 Vdc/battery
- Equalizing Charging Voltage:14.4 - 15.0 Vdc/battery
- Operating Temperature:discharge -15°C to 50°C; charge/storage -15°C to 40°C
- Note:F1 terminal is available; Max Discharge Current = 150 A (5 sec.)
Product details
The GPL12120 is a 12V valve-regulated sealed lead-acid (VRLA) battery in CSB's GPL series, featuring a top terminal design and Absorbent Glass Mat (AGM) technology that achieves up to 99% gas recombination efficiency with no routine maintenance required. Its nominal capacity is 12 Ah at the 20-hour rate (1.75 VPC @25°C); at the 8-hour rate, the capacity is 9.76 Ah (1.75 VPC @25°C) or 9.60 Ah (1.80 VPC @25°C). Dimensions are 151.0±2.0 mm in length, 98.0±1.0 mm in width, and 100.3±1.5 mm in height, weighing approximately 4.10 kg, and it is equipped with F2 Faston Tab 250 terminals.
Electrically, the battery has a maximum charge current of 3.60 A, a maximum discharge current of 180 A, a short-circuit current of 458 A, and an internal resistance of only 13.2 mΩ. At 25°C, the float voltage should be maintained at 13.5 - 13.8 Vdc per battery, and the equalize voltage at 14.4 - 15.0 Vdc per battery. The design float life can reach 8 years at 25°C and complies with the Eurobat long life standard (10/12 years at 20°C). The self-discharge rate is low, with remaining capacity still above 90% after 90 days of storage, and it can be stored for up to 6 months at 25°C; always fully charge before use, and if storage temperature exceeds 25°C, charge ahead of time.
The operating temperature range covers: nominal 25°C, -15°C to 50°C during discharge, and -15°C to 40°C during charge and storage. The case material is ABS (UL 94-HB), and a flame-retardant (94-V0) version is also available upon request. The product meets the IEC 61056-1/2:2012 standard and is UL1989 certified (MH14533).
The GPL12120 is designed for float backup power applications and is the extended-life version of the GP series, suitable for general-purpose backup power such as uninterruptible power supplies (UPS), emergency lighting, security systems, communication equipment, and various industrial backup power applications. Its pure lead construction and proprietary formulation work together to help extend service life, thereby providing stable and reliable power in backup service.