Product Features

  • Valve-regulated lead-acid (VRLA) battery design
  • AGM (Absorbent Glass Mat) technology, maintenance-free, with gas recombination efficiency up to 99%
  • Pure lead plates with proprietary formulation elements
  • Suitable for float standby power applications
  • Manufactured in compliance with IEC 61056-1/2:2012 and UL1989 certified (MH14533)

Application Scenarios

  • Provides backup power for security alarm panels
  • Used for emergency lighting and exit signs
  • Serves as backup power for medical monitors and infusion pumps
  • Supports access control systems and building intercom equipment
  • Power source for fire alarm and linkage control panels
  • Suitable for small electronic instruments and testing devices

Product parameters

  • Model:GPL12400
  • Voltage:12 Vdc
  • Nominal Capacity:40 Ah @20hr-rate
  • Ah Capacity:40.32 (8-Hr 1.75 VPC @ 25°C)
  • Ah Capacity:44.40 (20-Hr 1.75 VPC @ 25°C)
  • Ah Capacity:39.60 (8-Hr 1.80 VPC @ 25°C)
  • Max. Charge Current:12.00 A
  • Max. Discharge Current:400 A
  • Short Circuit Current:1182 A
  • Internal Resistance:8.5 mΩ
  • Terminal Type:I2 thread lead alloy terminal to accept M6 bolt
  • Terminal Torque:51.7±10.3 Kgf·cm / 44.9±9.0 Lbf·in / 5.10±1.0 N·m
  • Container Material:ABS (UL 94-HB) standard, flame-retardant (94-V0) available upon request
  • Weight:12.92 / 28.48 kg / lb.
  • Length (L):197.0±2.0 / 7.76±0.08 mm / in
  • Width (W):165.0±2.0 / 6.50±0.08 mm / in
  • Height (H):170.4±2.0 / 6.71±0.08 mm / in
  • Design Life:Up to 10 years in standby service at 25°C; Eurobat (20°C): 10/12 years, Long Life
  • Float Charging Voltage:13.5 - 13.8 Vdc/battery
  • Equalizing Charging Voltage:14.4 - 15.0 Vdc/battery
  • Operating Temperature:discharge -15°C to 50°C; charge/storage -15°C to 40°C

Product details

In the GPL series, the CSB GPL12400 is the long-life version of the GP series, designed primarily for general-purpose float standby power. This battery is a 12V valve-regulated sealed lead-acid battery utilizing Absorbent Glass Mat (AGM) technology, with a gas recombination efficiency of up to 99%, and is maintenance-free. Its construction uses pure lead, is manufactured in accordance with IEC 61056-1/2:2012, and is recognized under UL1989 (MH14533). In terms of capacity specifications, the GPL12400 has a nominal capacity of 40Ah (1.75 VPC @25°C, 20hr-rate). At 25°C, the 8-hour rate 1.75 VPC capacity is 40.32Ah, the 20-hour rate 1.75 VPC capacity is 44.40Ah, and the 8-hour rate 1.80 VPC capacity is 39.60Ah. The battery has a maximum charge current of 12.00A, a maximum discharge current of 400A, a short-circuit current of 1182A, and an internal resistance of 8.5 mΩ. Regarding dimensions and terminals, the GPL12400 has a length of 197.0±2.0 mm, a width of 165.0±2.0 mm, a height of 170.4±2.0 mm, and a weight of 12.92 kg. The terminals use I2 threaded lead alloy and can be paired with M6 bolts. The terminal torque is 51.7±10.3 Kgf·cm, equivalent to 44.9±9.0 Lbf·in or 5.10±1.0 N·m. The case material is ABS (UL 94-HB), and a flame-retardant 94-V0 version is also available upon request. For charging and operating conditions, the float charge voltage at 25°C is 13.5 to 13.8 Vdc/battery, and the equalization charge voltage is 14.4 to 15.0 Vdc/battery. The nominal operating temperature is 25°C, the discharge temperature range is -15°C to 50°C, and the charge and storage temperature range is -15°C to 40°C. In terms of self-discharge, it is less than 10% after 90 days, and storage time at 25°C can reach 6 months; it should be fully charged before use. If the storage temperature exceeds 25°C, charging is required earlier. Under float charge conditions at 25°C, the GPL12400 has a design life of up to 10 years, and according to the Eurobat 20°C standard, its long-life rating is 10/12 years. With its long-life and maintenance-free characteristics, this battery is suitable for float standby power scenarios and can meet the needs of general-purpose standby power.