Product Features

  • Valve-regulated lead-acid (VRLA) design
  • Maintenance-free with absorbed glass mat (AGM) technology and up to 99% gas recombination efficiency
  • Pure lead construction with proprietary elements
  • Engineered for high-rate UPS and float standby power applications
  • Manufactured to IEC 60896-21/22:2004 and UL1989 certified (MH14533)

Application Scenarios

  • Large data centers requiring long-duration backup power, suitable for this UPS
  • Long-runtime UPS backup power for data centers
  • Backup solution for long-duration discharge of industrial UPS equipment
  • Long-runtime backup power for the financial industry
  • Long-duration backup power for telecommunications hubs
  • Long-runtime UPS backup for medical centers

Product parameters

  • Model:XPL2000
  • Voltage:12 Vdc
  • Nominal Capacity:2000W @5min-rate
  • Watts per Cell:321.33 (5-Min 1.67 VPC @ 25°)
  • Watts per Cell:173.67 (15-Min 1.67 VPC @ 25°)
  • Max. Charge Current:16.70 A
  • Max. Discharge Current:400 A
  • Short Circuit Current:1243 A
  • Internal Resistance:6.33 mΩ
  • Terminal Type:I2 thread lead alloy terminal to accept M6 bolt
  • Terminal Torque:51.7±10.3 Kgf·cm / 44.9±9.0 Lbf·in / 5.1±1.0 N·m
  • Container Material:ABS (UL 94-HB) standard, flame-retardant (94-V0) available upon request
  • Weight:13.58 / 29.94 kg / lb.
  • Length (L):197.0±2.0 / 7.76±0.08 mm / in
  • Width (W):165.0±2.0 / 6.50±0.08 mm / in
  • Height (H):170.4±2.0 / 6.71±0.08 mm / in
  • Design Life:Up to 10 years in standby service at 25°C; Eurobat (20°C): 10/12 years, Long Life
  • Float Charging Voltage:13.5 - 13.8 Vdc/battery
  • Equalizing Charging Voltage:14.4 - 15.0 Vdc/battery
  • Operating Temperature:discharge -15°C to 50°C; charge/storage -15°C to 40°C

Product details

The XPL2000 is a battery in CSB's XPL series and is a 12V top-terminal valve-regulated sealed lead-acid battery. This product uses absorbed glass mat (AGM) technology, achieving gas recombination efficiency of up to 99%, and features a maintenance-free design. This series is a high-capacity pure lead VRLA series, mainly targeting long-duration backup scenarios that require large individual cells; the officially published application area is data center uninterruptible power supplies. In terms of electrical and power parameters, the XPL2000 has a nominal capacity of 2000W @5min-rate, tested at 25°C with 9.60V per battery. Its 5-minute rate power reaches 321.33 W/cell, and its 15-minute rate power is 173.67 W/cell; both tests are based on 1.67 VPC at 25°C. The battery can withstand a maximum charge current of 16.70 A, a maximum discharge current of 400 A, a short-circuit current of 1243 A, and an internal resistance of 6.33 mΩ. At 25°C, the float charge voltage range is 13.5 to 13.8 Vdc/battery, and the equalize charge voltage range is 14.4 to 15.0 Vdc/battery. In terms of mechanical structure, the XPL2000 is equipped with I2 threaded lead alloy terminals that accept M6 bolts, with a terminal torque of 51.7±10.3 Kgf∙cm, or 44.9±9.0 Lbf∙in, or 5.1±1.0 N∙m. The case is made of ABS material and meets the UL 94-HB standard; a flame-retardant 94-V0 version can be requested separately. The battery weighs 13.58 kg (29.94 lb), and its dimensions are length 197.0±2.0 mm (7.76±0.08 in), width 165.0±2.0 mm (6.50±0.08 in), and height 170.4±2.0 mm (6.71±0.08 in). Regarding operating temperature, the nominal temperature is 25°C, the allowable discharge range is -15°C to 50°C, and the allowable charge and storage range is -15°C to 40°C. In terms of design life, it can reach 10 years under float standby service at 25°C; according to the Eurobat standard, it is classified as 10/12-year long life at 20°C. Self-discharge characteristics are: stored at 25°C for 90 days, self-discharge is less than 10%; the battery can be stored for up to 6 months, and with equalizing charge this can be extended to 10 months. It must be fully charged before use; if storage temperature exceeds 25°C, charge it earlier. This product is manufactured in accordance with IEC 60896-21/22:2004 and is UL1989 recognized under recognition number MH14533. With its pure lead construction and proprietary element design, the XPL2000 is suitable for high-rate UPS and float standby power applications, especially data center uninterruptible power supplies and other applications requiring long-duration backup power. When using it, please operate according to the charging voltage and temperature conditions provided in the data to ensure the battery maintains normal operating condition.
link
Go to purchase
Telephone
13775032303
email
powercube@foxmail.com
wechat
wechat
Loading...