CSB XPL2000 12V 2000W Valve-Regulated Sealed Lead-Acid Battery
The CSB XPL2000 is a 12V valve-regulated sealed lead-acid battery in the XPL series, combining pure lead and AGM technology with a 5-minute rate power of 2000W. It is suitable for data center UPS and other applications requiring long-duration backup power, with a design float service life of up to 10 years.
Taobao store
WeChat procurement
Product Features
- Valve-regulated lead-acid (VRLA) design
- Maintenance-free with absorbed glass mat (AGM) technology and up to 99% gas recombination efficiency
- Pure lead construction with proprietary elements
- Engineered for high-rate UPS and float standby power applications
- Manufactured to IEC 60896-21/22:2004 and UL1989 certified (MH14533)
Application Scenarios
- Large data centers requiring long-duration backup power, suitable for this UPS
- Long-runtime UPS backup power for data centers
- Backup solution for long-duration discharge of industrial UPS equipment
- Long-runtime backup power for the financial industry
- Long-duration backup power for telecommunications hubs
- Long-runtime UPS backup for medical centers
Product parameters
- Model:XPL2000
- Voltage:12 Vdc
- Nominal Capacity:2000W @5min-rate
- Watts per Cell:321.33 (5-Min 1.67 VPC @ 25°)
- Watts per Cell:173.67 (15-Min 1.67 VPC @ 25°)
- Max. Charge Current:16.70 A
- Max. Discharge Current:400 A
- Short Circuit Current:1243 A
- Internal Resistance:6.33 mΩ
- Terminal Type:I2 thread lead alloy terminal to accept M6 bolt
- Terminal Torque:51.7±10.3 Kgf·cm / 44.9±9.0 Lbf·in / 5.1±1.0 N·m
- Container Material:ABS (UL 94-HB) standard, flame-retardant (94-V0) available upon request
- Weight:13.58 / 29.94 kg / lb.
- Length (L):197.0±2.0 / 7.76±0.08 mm / in
- Width (W):165.0±2.0 / 6.50±0.08 mm / in
- Height (H):170.4±2.0 / 6.71±0.08 mm / in
- Design Life:Up to 10 years in standby service at 25°C; Eurobat (20°C): 10/12 years, Long Life
- Float Charging Voltage:13.5 - 13.8 Vdc/battery
- Equalizing Charging Voltage:14.4 - 15.0 Vdc/battery
- Operating Temperature:discharge -15°C to 50°C; charge/storage -15°C to 40°C
Product details
The XPL2000 is a battery in CSB's XPL series and is a 12V top-terminal valve-regulated sealed lead-acid battery. This product uses absorbed glass mat (AGM) technology, achieving gas recombination efficiency of up to 99%, and features a maintenance-free design. This series is a high-capacity pure lead VRLA series, mainly targeting long-duration backup scenarios that require large individual cells; the officially published application area is data center uninterruptible power supplies.
In terms of electrical and power parameters, the XPL2000 has a nominal capacity of 2000W @5min-rate, tested at 25°C with 9.60V per battery. Its 5-minute rate power reaches 321.33 W/cell, and its 15-minute rate power is 173.67 W/cell; both tests are based on 1.67 VPC at 25°C. The battery can withstand a maximum charge current of 16.70 A, a maximum discharge current of 400 A, a short-circuit current of 1243 A, and an internal resistance of 6.33 mΩ. At 25°C, the float charge voltage range is 13.5 to 13.8 Vdc/battery, and the equalize charge voltage range is 14.4 to 15.0 Vdc/battery.
In terms of mechanical structure, the XPL2000 is equipped with I2 threaded lead alloy terminals that accept M6 bolts, with a terminal torque of 51.7±10.3 Kgf∙cm, or 44.9±9.0 Lbf∙in, or 5.1±1.0 N∙m. The case is made of ABS material and meets the UL 94-HB standard; a flame-retardant 94-V0 version can be requested separately. The battery weighs 13.58 kg (29.94 lb), and its dimensions are length 197.0±2.0 mm (7.76±0.08 in), width 165.0±2.0 mm (6.50±0.08 in), and height 170.4±2.0 mm (6.71±0.08 in).
Regarding operating temperature, the nominal temperature is 25°C, the allowable discharge range is -15°C to 50°C, and the allowable charge and storage range is -15°C to 40°C. In terms of design life, it can reach 10 years under float standby service at 25°C; according to the Eurobat standard, it is classified as 10/12-year long life at 20°C. Self-discharge characteristics are: stored at 25°C for 90 days, self-discharge is less than 10%; the battery can be stored for up to 6 months, and with equalizing charge this can be extended to 10 months. It must be fully charged before use; if storage temperature exceeds 25°C, charge it earlier.
This product is manufactured in accordance with IEC 60896-21/22:2004 and is UL1989 recognized under recognition number MH14533. With its pure lead construction and proprietary element design, the XPL2000 is suitable for high-rate UPS and float standby power applications, especially data center uninterruptible power supplies and other applications requiring long-duration backup power. When using it, please operate according to the charging voltage and temperature conditions provided in the data to ensure the battery maintains normal operating condition.