Product Features

  • Valve-regulated lead-acid (VRLA) design
  • Maintenance-free, with absorbent glass mat (AGM) technology for up to 99% gas recombination efficiency
  • Pure lead construction with proprietary element formulation
  • Purpose-built for high-rate UPS and float standby power applications
  • Manufactured to IEC 60896-21/22:2004 and UL1989 certified (MH14533)

Application Scenarios

  • UPS backup applications Data centers requiring long-duration discharge
  • Long-duration backup power for large equipment rooms
  • Industrial UPS long-duration discharge needs Backup power
  • Long-duration backup power solutions for financial systems
  • Long-duration backup power applications for communication hubs
  • Long-duration UPS backup power for medical centers

Product parameters

  • Model:XPL4200
  • Voltage:12 Vdc
  • Nominal Capacity:4200W @5min-rate
  • Watts per Cell:979.83 (30-Sec 1.67 VPC @ 25°C)
  • Watts per Cell:660.50 (5-Min 1.67 VPC @ 25°)
  • Watts per Cell:370.17 (15-Min 1.67 VPC @ 25°)
  • Max. Charge Current:35.00 A
  • Max. Discharge Current:900 A
  • Short Circuit Current:2616 A
  • Internal Resistance:3.22 mΩ
  • Terminal Type:I2 thread lead alloy terminal to accept M6 bolt
  • Terminal Torque:51.7±10.3 Kgf·cm / 44.9±9.0 Lbf·in / 5.1±1.0 N·m
  • Container Material:PP (UL 94-HB) standard, flame-retardant (94-V0) available upon request
  • Weight:28.20 / 62.17 kg / lb.
  • Length (L):261.0±2.5 / 10.28±0.10 mm / in
  • Width (W):168.5±2.0 / 6.63±0.08 mm / in
  • Height (H):213.5±2.5 / 8.41±0.10 mm / in
  • Design Life:Up to 10 years in standby service at 25°C; Eurobat (20°C): >12 years, Very Long Life
  • Float Charging Voltage:13.5 - 13.8 Vdc/battery
  • Equalizing Charging Voltage:14.4 - 15.0 Vdc/battery
  • Operating Temperature:discharge -15°C to 50°C; charge/storage -15°C to 40°C

Product details

The CSB XPL4200 is a 12V valve-regulated sealed lead-acid battery in the XPL series, utilizing Absorbent Glass Mat (AGM) technology with gas recombination efficiency of up to 99%, and is maintenance-free. Because of its pure lead construction and proprietary element design, this battery is suitable for high-rate UPS and float standby power applications. The product meets IEC 60896-21/22:2004 standards and is UL1989 recognized (MH14533). In terms of electrical specifications, the XPL4200 has a nominal capacity of 4200W @5min-rate (9.60V per PCS @ 25°C). At 25°C and 1.67 VPC, the W/cell power ratings are: 979.83 W/cell at 30 seconds, 660.50 W/cell at 5 minutes, and 370.17 W/cell at 15 minutes. The maximum charge current is 35.00 A, the maximum discharge current is 900 A, the short-circuit current is 2616 A, and the internal resistance is 3.22 mΩ. For terminals, the battery uses an I2 thread lead alloy terminal to accept M6 bolt, with a torque value of 51.7±10.3 Kgf∙cm / 44.9±9.0 Lbf∙in / 5.1±1.0 N∙m. The case material is PP (UL 94-HB), and a flame-retardant (94-V0) version is also available upon request. Weight is 28.20 kg (62.17 lb), and the dimensions are 261.0±2.5 mm in length, 168.5±2.0 mm in width, and 213.5±2.5 mm in height. At 25°C, the XPL4200 has a design life of up to 10 years in standby service and meets the Eurobat (20°C) >12 year Very Long Life standard. Operating temperature range: nominal 25°C, -15°C to 50°C during discharge, and -15°C to 40°C during charge and storage. Float voltage is 13.5 - 13.8 Vdc/battery (25°C), and equalize voltage is 14.4 - 15.0 Vdc/battery (25°C). For self-discharge, it is less than 10% after 90 days of storage at 25°C, and can be stored for up to 6 months; if equalization charge is performed every 10 months, storage time can be further extended. It must be fully charged before use, and if storage temperature exceeds 25°C, it should be charged earlier. The official designated application is data center UPS (uninterruptible power supply), and its large-capacity pure lead VRLA series is positioned for long-duration standby scenarios requiring large batteries.