Product Features

  • VRLA (valve-regulated lead-acid) battery
  • Maintenance-free, no water topping-up required; utilizes AGM (absorbent glass mat) technology with gas recombination efficiency up to 99%
  • Pure lead grid paired with proprietary formulation elements
  • Specifically engineered for high-rate UPS and float-charge standby power applications
  • Manufactured in accordance with IEC 60896-21/22:2004 and certified to UL1989 (MH14533)

Application Scenarios

  • UPS with long backup time, suitable for data centers
  • For large equipment rooms requiring extended backup power
  • Backup solution for industrial UPS with long discharge durations
  • Long-duration backup power for the financial sector
  • Extended standby power for telecommunications hubs
  • Long-duration UPS applications in medical centers

Product parameters

  • Model:XPL2200
  • Voltage:12 Vdc
  • Nominal Capacity:2200W @5min-rate
  • Watts per Cell:563.00 (30-Sec 1.67 VPC @ 25°C)
  • Watts per Cell:366.17 (5-Min 1.67 VPC @ 25°)
  • Watts per Cell:201.50 (15-Min 1.67 VPC @ 25°)
  • Max. Charge Current:18.30 A
  • Max. Discharge Current:500 A
  • Short Circuit Current:1344 A
  • Internal Resistance:5.60 mΩ
  • Terminal Type:I2 thread lead alloy terminal to accept M6 bolt
  • Terminal Torque:51.7±10.3 Kgf·cm / 44.9±9.0 Lbf·in / 5.1±1.0 N·m
  • Container Material:PP (UL 94-HB) standard, flame-retardant (94-V0) available upon request
  • Weight:16.65 / 36.70 kg / lb.
  • Length (L):228.0±2.5 / 8.98±0.10 mm / in
  • Width (W):138.4±1.5 / 5.45±0.06 mm / in
  • Height (H):206.3±2.5 / 8.12±0.10 mm / in
  • Design Life:Up to 10 years in standby service at 25°C; Eurobat (20°C): >12 years, Very Long Life
  • Float Charging Voltage:13.5 - 13.8 Vdc/battery
  • Equalizing Charging Voltage:14.4 - 15.0 Vdc/battery
  • Operating Temperature:discharge -15°C to 50°C; charge/storage -15°C to 40°C

Product details

The CSB XPL2200 belongs to the XPL series and is a 12V top-terminal VRLA battery featuring pure lead construction combined with AGM technology. This series is designed for long-duration backup scenarios requiring high-capacity single cells, with data center uninterruptible power supplies as the official designated application. At 25°C, the battery delivers a nominal capacity of 2200W @5min-rate; its per-cell power performance is: 563.00 W/cell at 30 seconds to 1.67 VPC, 366.17 W/cell at 5 minutes to 1.67 VPC, and 201.50 W/cell at 15 minutes to 1.67 VPC. In terms of electrical specifications, the XPL2200 has a maximum charge current of 18.30 A, a maximum discharge current of 500 A, a short-circuit current of 1344 A, and an internal resistance of 5.60 mΩ. Float voltage at 25°C is 13.5 to 13.8 Vdc/battery, and equalize voltage at 25°C is 14.4 to 15.0 Vdc/battery. Terminals use I2 threaded lead alloy, accommodate M6 bolts, and have a torque value of 51.7±10.3 Kgf∙cm, 44.9±9.0 Lbf∙in, or 5.1±1.0 N∙m. Regarding dimensions and weight, the XPL2200 measures 228.0±2.5 mm in length, 138.4±1.5 mm in width, and 206.3±2.5 mm in height, and weighs 16.65 kg (36.70 lb). The case material is PP (UL 94-HB), with a flame-retardant (94-V0) version available upon request. In terms of design life, float standby service at 25°C can reach 10 years, and it meets the Eurobat (20°C) long-life classification of greater than 12 years. For temperature conditions, the nominal temperature is 25°C, the discharge temperature range is -15°C to 50°C, and the charge and storage temperature range is -15°C to 40°C. Self-discharge characteristics are: less than 10% self-discharge after 90 days of storage at 25°C, with a maximum storage period of 6 months; with equalizing charge, the storage period can be extended to 10 months. The battery must be fully charged before use, and if the storage temperature exceeds 25°C, it should be charged ahead of time. The XPL2200 features VRLA design and AGM technology, with a gas recombination efficiency of up to 99%, and is maintenance-free. Its pure lead construction and proprietary element formulation are specifically engineered for high-rate UPS and float standby power applications. It is manufactured in accordance with IEC 60896-21/22:2004 and is UL1989 recognized (MH14533).