Product Features

  • Valve-regulated lead-acid (VRLA) technology
  • Absorbent glass mat (AGM) design, maintenance-free with no water addition, gas recombination efficiency up to 99%
  • Plates made of pure lead with proprietary additives
  • Designed specifically for float-charge standby power applications
  • Manufactured to IEC 61056-1/2:2012, UL1989 certified (MH14533)

Application Scenarios

  • Standby power for security and alarm systems
  • Emergency lighting and exit signage
  • Backup power for medical equipment such as monitors and infusion pumps
  • Access control systems and building intercom equipment
  • Fire alarm control panels and linked control systems
  • Portable electronic instruments and testing tools

Product parameters

  • Model:GP1245
  • Voltage:12 Vdc
  • Nominal Capacity:4.5Ah @20hr-rate
  • Ah Capacity:4.25 (8-Hr 1.75 VPC @ 25°C)
  • Ah Capacity:4.58 (20-Hr 1.75 VPC @ 25°C)
  • Ah Capacity:4.23 (8-Hr 1.80 VPC @ 25°C)
  • Max. Charge Current:1.35 A
  • Max. Discharge Current:90 A
  • Short Circuit Current:160 A
  • Internal Resistance:37.7 mΩ
  • Terminal Type:F2 terminal (Faston Tab 250)
  • Container Material:ABS (UL 94-HB) standard, flame-retardant (94-V0) available upon request
  • Weight:1.66 / 3.66 kg / lb.
  • Length (L):92.8±1.0 / 3.65±0.04 mm / in
  • Width (W):69.9±1.0 / 2.75±0.04 mm / in
  • Height (H):107.7±1.5 / 4.24±0.06 mm / in
  • Design Life:Up to 5 years in standby service at 25°C; Eurobat (20°C): 3-5 years, Standard Commercial
  • Float Charging Voltage:13.5 - 13.8 Vdc/battery
  • Equalizing Charging Voltage:14.4 - 15.0 Vdc/battery
  • Operating Temperature:discharge -15°C to 50°C; charge/storage -15°C to 40°C
  • Note:F1 terminal is available; Max Discharge Current = 60 A

Product details

Among GP Series general purpose valve-regulated sealed lead-acid batteries, the CSB GP1245 features a 6V and 12V top terminal VRLA-AGM construction. Its nominal voltage is 12 Vdc, with a 20-hour rate nominal capacity of 4.5Ah. This series is designed for a variety of applications including security, emergency lighting, and medical equipment, and can be used for float standby power. Capacity data: at 25°C reference, 8-hour rate at 1.75 VPC is 4.25 Ah, 20-hour rate at 1.75 VPC is 4.58 Ah, 8-hour rate at 1.80 VPC is 4.23 Ah. The battery can withstand a maximum charge current of 1.35 A, maximum discharge current 90, short-circuit current 160 A, internal resistance 37.7 mΩ. Terminals are F2 quick-connect tab 250 type, case is ABS material, standard configuration is UL 94-HB, flame-retardant 94-V0 version optional. Dimensions and weight: length 92.8±1.0 mm, width 69.9±1.0 mm, height 107.7±1.5 mm, weight 1.66 kg. Charging: at 25°C, float voltage 13.5 to 13.8 Vdc, equalization voltage 14.4 to 15.0 Vdc. Temperature range: nominal 25°C, discharge -15°C to 50°C, charge and storage -15°C to 40°C. This battery combines valve-regulated sealed lead-acid design with absorbed glass mat technology to achieve gas recombination, is maintenance-free, and is manufactured with pure lead construction and proprietary elements, compliant with IEC 61056-1/2:2012 and UL1989 (MH14533) recognized. Design life up to 5 years at 25°C float standby service, 3 to 5 years under Eurobat 20°C standard commercial conditions. Self-discharge: less than 10% after 90 days at 25°C, can be stored up to 6 months, must be fully charged before use, and if storage temperature exceeds 25°C, charge earlier.
link
Go to purchase
Telephone
13775032303
email
powercube@foxmail.com
wechat
wechat
Loading...